OPERATING INSTRUCTIONSPOwER SUPPly mANAGERVX-3000DS CEVX-3000DS CE-GBThank you for purchasing TOA’s Power Supply Manager.Please carefully follow the i
10 Step 1. Allow more than 10seconds to elapse after removing the powercords from the VX-3000DS'rear-mounted AC inlets (IN1 and I
11 Step 1. ConrmthatbatterypowerisnotinusebymeansoftheVX-3000DS'front-mountedBATTERYPOWERLED, which is unlit in this case. Step
12[Fixing the battery] TocomplywithEN54-4,xthebatteryatthebottomplatesurfaceoftherackasshownbelow.Attach hook fasteners to the botto
135. CONNECTIONS5.1. Connecting the VX-3000DS to VX-2000 SystemDS-SFLINK1228 V 4.8 ADC POWER INCH3 CH1CH4 CH2PA OUT (SP LINE)C HCH1C HCH2C HCH3C HCH4D
145.2. Connecting the VX-3000DS to SX-2000 System5.2.1 When using a redundant power system*In this connection example, 2 power supply units are used.
155.2.2. When not using a redundant power systemRequiredpowerissuppliedtothesystemfromasinglepowersupplyunit.Connectthe[+]terminalof
16[Cable termination]When connecting 2 power cables to a single terminal of the removable terminal plug, use a ferrule terminal with an insulation sle
175.3. Connecting the VX-3000DS to VM-3000 SystemVX-3000DSVP-2241PA LINK VP-200VX28 V 4.8 ADC POWER INPA OUT (SP LINE)C HTEMPERATURESENSOR24V(16-25V)P
185.3.1 Required number of VX-3000DS units in a 1-channel broadcasting systemThe required number of the VX-3000DS Power Supply Manager units is deter
19[System including one VP amplifier connected as a standby amplifier]OneVX-3000DSisrequiredevery4VM-3360VA/3360Eampliersor6VM-3240VA/3240E
2TABLE OF CONTENTS1. SAFETY PRECAUTIONS ... 32. FEATURES ...
20Belowisanexampleshowingthat2VX-3000DSunitsareusedinasystemincluding5VM-3240VA/3240Eampliers.[Required number of VX-3000DS units in
216. CABLE USAGE TABLE[VX-3000DS]Terminal to Connect Cable Type Equipment to be Connected toTerminal NameEquipment ReceptaclePlug Cable Type Plug Equi
227. SWITCHING OFF SYSTEM POWER (DC)Connector Name• VX-3000DS' DS LINK ConnectionsDS LINK IN/OUTRJ45 Pin No.Orange/whiteShieldBrownBrown/whiteGre
238. BLOCK DIAGRAMFuse T6.3A LFuse T6.3A LFuse T6.3A LDC Out 3DC Out 2DC Out 1POWER OUT 19-33 V MAX 5 ADC Output 3DC Output 2DC Output 1POWER OUT 19-3
249. APPENDIX: Recommendations to the Power Supply InstallationIncorrect installations of the power supply manager VX-3000DS and its related equipme
25Battery ConnectionClean ContactsTake care that the connection terminals are clean before connecting the cables. Clean them if necessary.Ensure that
26VX-3000DSThe power manager VX-3000DS monitors the availability of the AC power and switches on the battery in case of a total loss of that power. Wh
27Trouble ShootingThe different faults described below are indicated on the front panel (Figure 4). Refer to the explanation below.AC POWER BATTERYIN1
28Check procedure 2:This measurement can be done with a slow voltmeter. DisconnecttheVAunit’spowersupplyfromtheDCoutputfromtheVX-3000DSan
29Power Source 220–230VAC,50/60HzPower Consumption 2800 W max. in total (at rated output with charging)650 W max. in total, 350 W max. each (EN6
31. SAFETY PRECAUTIONS• Beforeinstallationoruse,besuretocarefullyreadalltheinstructionsinthis sectionforcorrect andsafeoperation.•
URL:http://www.toa.jp/133-02-00037-02
4• When connecting multiple appliances to a singlepower socket through a multi-outlet power strip, a total current consumption of the applianc
53. NOMENCLATURE AND FUNCTIONS[Front]12 34 5 6AC POWER BATTERYIN1IN2POWERCONNECTCONDITIONPOWER SUPPLY MANAGER VX-3000DSCHECKCHARGING1. Power indicator
6[Fault indication]If any of the following indicators on the front panel remains unlit, the unit is judged failed. In such cases, remove the cause of
7[Rear] 10. Functional earth terminal [SIGNAL GND]Hum noise may be generated when external equipment is connected to the unit. Connecting this termina
84. INSTALLATION4.1. Installing the VX-3000DS in the Cabinet Rack4.2. Battery Installation• Takespecialcaretopreventthebatteryfrombeingshort
9• Strip the cable end long enough (30mm ±5 mm)to befully clamped. Otherwise, its outer jacket prevents the cable conductor from being t